Capacity-Limited Cooling Explains Simultaneous Energy Waste and Thermal Discomfort in Two University Buildings in the Southern Philippines

Fejaycris O. Pillodar, Dioniela Mae C. Ellos, Jiza Gay P. Jarabe, John Russel A. Dalogdog, Monaliza Joy Z. Magsayo, Charlene Mae Z. Gaab, Manuel Anthony P. Jondonero, Melgie A. Alas, Rovick Pelos P. Tarife, Noel R. Estoperez, Mark June L. Aporador, Napoleon A. Enteria, Kim Emissary C. Magarin, Ryan Lloyd R. Carpentero, Hernando P. Bacosa, and Peter D. Suson

https://doi.org/10.47836/pjst.34.5.08
KeywordsBuilding energy audit, canopy cover, energy conservation measures, greenhouse gas emissions, illuminance, indoor environmental quality, lighting power density, set-point attainment
Article content

Abstract

Institutional buildings in the humid tropics are commonly assumed to waste energy because occupants set thermostats to low setpoints. This study tested that assumption in the two largest academic buildings at the Mindanao State University-Iligan Institute of Technology (MSU-IIT), combining 2,491 equipment records, 642 temperature and humidity observations, illuminance in 212 rooms, and a survey of 175 occupants. Room-level records were analysed using Welch t-tests, Mann-Whitney U tests, Hedges’ g, chi-square tests, and ordinary least squares regression at a significance level of 0.05. Combined annual use was 1,151 MWh, costing PHP 13.81 million and emitting 639.5 t CO₂, with air conditioning taking 47.2% and 56.3% of demand. Set-points averaged 20.11 °C and fell below the 24 °C national guideline in 70.9% of observations, yet were attained in only 2.0%, and delivered temperature was almost insensitive to set-point (slope 0.097, 95% CI 0.053 to 0.140). Air conditioning held rooms only 1.75 °C below free-running rooms, indicating capacity-limited rather than control-limited operation, and self-reported set-points corroborated the measured values to within 0.5 °C. Separately, 87.3% of rooms fell below 300 lx, despite an average lighting power density of only 2.9 W m⁻², a provision deficit. These findings invert the conventional retrofit hierarchy, because thermostat policy cannot save energy while units remain capacity-limited, so cooling capacity and the building envelope must be restored first. Sequenced this way, five measures deliver 21.6% of baseline consumption at a 3.3-year payback, twice the reduction required of state universities. Testing set-point attainment before prescribing behavioural measures is a transferable diagnostic for tropical institutional estates.